Part Number: EJX430A-EAB5G-92DDN/KU22/D3/M01/T01/N4Model: EJX430A Gauge Pressure Transmitter
Brand: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months
Ordering Information
| Model | EJX430A | Gauge pressure transmitter |
| Output signal | -E | 4 to 20 mA DC with digital communication (HART 5 protocol) |
| Measurement span (capsule) | A | 0.0175 to 3.5 MPa (2.5 to 500 psi) |
| Wetted parts material(1) | B# | Cover flange and process connector: Monel equivalent(2) Capsule: Monel Capsule gasket: PTFE Teflon Vent/Drain plug: Monel |
| Process connections | 5 | without process connector (1/4 NPT female on the cover flanges) |
| Bolts and nuts material | G | 316L SST |
| Installation | *-9 | Horizontal piping and left side high pressure |
| Amplifier housing | 2 | ASTM CF-8M stainless steel(3) |
| Electrical connection | D | M20 female, two electrical connections and a 316 SST blind plug |
| Integral indicator | D | Digital indicator(4) |
| Mounting bracket | N | (None) |
| ATEX | /KU22 | Combined KF22, KS21 and ATEX Intrinsically safe Ex ic(5)(6) [ATEX Intrinsically safe Ex ic] Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012 II 3G Ex ic IIC T4 Gc, Amb. Temp.: ?C30 to 60??C (?C22 to 140??F)(7) Ui=30 V, Ci=27.6 nF, Li=0 ??H |
| Calibration units(8) | /D3 | bar calibration (bar unit) |
| Material certificate(9) | /M01 | Cover flange(10) |
| Pressure test/ Leak test certificate(11) | /T01 | Test Pressure: 3.5 MPa (500 psi)(12)
Nitrogen(N2) Gas(13) Retention time: one minute |
| Wired tag plate | /N4 | 316 SST tag plate wired onto transmitter |
The ??#??marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156. Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
The ??*?? marks indicate the most typical selection for each specification.
- Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user??s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150??C [302??F] or above). Contact Yokogawa for detailed information of the wetted parts material. - Indicated material is equivalent to ASTM M35-2.
- Not applicable for electrical connection code 0, 5, 7 and 9.
- Not applicable for output signal code G.
- Applicable for Electrical connection code 2, 4, 7, 9, C and D.
- Not applicable for option code /AL.
- Lower limit of ambient temperature is ?C15??C (5??F) when /HE is specified
- The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1, D3, and D4.
- Material traceability certification, per EN 10204 3.1B.
- Applicable for process connections code 0 and 5.
- The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
- Applicable for capsule code A.
- Pure nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6).
- Estimated Lead Time: 10 - 12
- Shipping Weight: 5 Kg