Option Codes: /KU25: ATEX
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5...T4 Ga
Ambient Temperature: -55 to 60?C
Enclosure: IP66/IP67 in accordance with only IEC 60529
FISCO field device
Entity Parameters:
Supply/Output circuit: Ui=30V, li=300mA, Pi=1.2W, Ci-22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10?F, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s., 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70?C/T90?C Db
Ambient Temperature for Gas Atmospheres: -40 to 75?C for T6, -40 to 80?C for T5
Ambient Temperature for Dust Atmospheres: -30 to 65?C for T70?C, -30 to 80?C for T90?C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female?