Part Number : 1764-24BWA
Model | 1764-24BWA |
Number of I/O
| 12 inputs 12 outputs |
Line Power | 85 to 265V ac at 47 to 63 Hz |
Power Supply Usage
| 88 VA |
Power Supply Inrush
| 120V ac = 25A for 8 ms 240V ac = 40A for 4 ms |
User Power Output | 24V dc at 400 mA, 400 ??F max. |
Input Circuit Type | 24V dc, sink/source |
Output Circuit Type | relay |
Typical CPU Hold-up Time
| 10 to 3000 ms |
Operating Temp. | +0??C to +55??C (+32??F to +131??F) ambient |
Storage Temp. | -40??C to +85??C (-40??F to +185??F) ambient?? |
Operating Humidity | 5% to 95% relative humidity (non-condensing) |
Vibration | Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak Relay Operation: 2G |
Shock (without Data Access Tool installed)
| Operating: 30G panel mounted (15G DIN Rail mounted) Relay operation: 7.5G panel mounted (5G DIN Rail mounted) Non-Operating: 40G panel mounted (30G DIN Rail mounted) |
Shock (with Data Access Tool installed)
| Operating: 20G panel mounted (15G DIN Rail mounted) Relay operation: 7.5G panel mounted (5G DIN Rail mounted) Non-Operating: 30G panel mounted (20G DIN Rail mounted) |
Agency Certification
| UL 508 C-UL under CSA C22.2 no. 142 Class I, Div. 2, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 no. 213) CE/RCM/EAC compliant for all applicable directives |
Electrical/EMC
| The module has passed testing at the following levels: EN61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect EN61000-4-3: 10 V/m EN61000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz EN61000-4-5: communications cable1 kv galvanic gun -I/O: 2 kV CM, 1 kV DM, -Power Supply (1764-24AWA/1764-24BWA): 4 kV CM, 2 kV DM -Power Supply (1764-28BXB): 0.5 kV CM, 0.5 kV DM EN61000-4-6: 10V, communications cable 3V |
Terminal Screw Torque | 1.13 Nm (10 in-lb) rated; 1.3 Nm (12 in-lb) maximum |
Programming Software
| For 1764-LSP Series A Processors: RSLogix 500, Version 3.01.09 or higher For 1764-LSP and 1764-LRP Series B Processors: RSLogix 500, Version 4.00.00 or higher. |
(1) Recommended storage temperature for maximum battery life (5 years typical with normal operating/storage conditions) of the 1764-RTC, 1764-MM1RTC, 1764-MM2RTC,
and 1764-MM3RTC is -40??C to +40??C (-40??F to +104??F). Battery life is significantly shorter at elevated temperatures.
Availability : In StockEstimated Lead Time : Usually Ships in 1 - 7 Working DaysShipping Weight : 3 Kg