Model | 1762-IR4 |
Dimensions, H x W x D
| 90 x 40 x 87 mm (3.54 x1.58 x 3.43 in.) height including mounting tabs is 110 mm (4.33 in.) |
Approximate Shipping Weight (with carton) | 260 g (0.57 lbs.) |
Storage Temperature | -40 85 ?C (-40 185 ?F) |
Operating Temperature | 0 55 ?C (+32 131 ?F) |
Operating Humidity | 5% to 95% non-condensing |
Operating Altitude | 2000 meters (6561 feet) |
Vibration | Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak |
Shock | Operating: 30 g |
Bus Current Draw (max.)
| 40 mA @ 5V DC 50 mA @ 24V DC |
Heat Dissipation
| 1.5 Watts |
Input Group to System Isolation
| 30V AC/30V DC rated working voltage? (N.E.C. Class 2 required) (IEC Class 2 reinforced insulation) type test: 500V AC or 707V DC for 1 minute |
Module Power LED | On: indicates power is applied. |
Vendor I.D. Code | 1 |
Product Type Code | 10 |
Product Code
| 65 |
Hazardous Environment Class
| Class I, Division 2, Hazardous Location, Groups A, B, C, D ISA/ANSI 12.12.01 (C-UL under CSA C22.2 No. 213) |
Radiated and Conducted Emissions | EN50081-2 Class A |
ESD Immunity (EN61000-4-2) | 4 kV contact, 8 kV air, 4 kV indirect |
Radiated Immunity (EN61000-4-3) | 10 V/m, 80 1000 MHz, 80% amplitude modulation, +900 MHz, keyed carrier |
Fast Transient Burst (EN61000-4-4) | 2 kV, 5 kHz |
Surge Immunity (EN61000-4-5) | 1 kV galvanic gun |
Conducted Immunity (EN61000-4-6) | 10V, 0.15 80 MHz? |