Model | 1771-SDN |
Module location | SLC 5/02 or later chassis |
Module defaults
| Node Address 63 Baud Rate 125 Kbps |
Power consumption - Backplane current - DeviceNet | 5V DC, 500 mA 24V DC, 90 mA Class 2 |
Isolation voltage
| 30V (continuous), Basic Insulation Type Tested at 500V AC for 60 s, DeviceNet to backplane |
Temperature, operating
| IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0...60?C (32...140?F) |
Temperature, non-operating
| IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40...85?C (-40...185?F) |
Relative humidity
| IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5 95% non-condensing |
Vibration
| IEC60068-2-6 (Test Fc, Operating): 2 g @10 500 Hz |
Shock
| IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002) Operating 30 g Non-operating 50 g |
Emissions
| CISPR 11: Group 1, Class A (with appropriate enclosure) |
ESD immunity
| IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges |
Radiated RF immunity
| IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80% AM from 80 2000 Mhz |
EFT/B immunity
| IEC 61000-4-4: +2 kV at 5 kHz on communication ports |
Surge transient immunity
| IEC 61000-4-5: ?2 kV line-earth(CM) on communications ports |
Conducted RF immunity
| IEC 61000-4-6: 10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz 80 MHz |
Magnetic field immunity
| IEC 61000-4-8: 30A/m long duration at 50 Hz |
Enclosure type rating | None (open style) |
Wiring - Size - Category? | Refer to DeviceNet Media Design Installation Guide 2 on communication ports |
10-pin Linear plug - Torque - Catalog number | 0.6 0.8 Nm (5 7 lb-in) 1787-PLUG10R |
North American temperature code | T5 |