ATEX | /KU2 | 4-20mA: [Intrinsically safe approval] Applicable Standard: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012 Certificate No. FM16ATEX0019X II 1 G Ex ia IIC T5...T4 Ga II 2 (1) D Ex ia [ia Da] IIIC T135??C Db Ambient Temperature: ?C40 to +70??C for T4, ?C40 to +50??C for T5, ?C30 to +70??C for IIIC Enclosure: IP66/IP67 Electrical parameters: Supply/Output circuit: Terminals: +, ?C Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH Sensor circuit: Terminals: 1, 2, 3, 4, 5 Uo=6V, Io=90mA, Po=135mW, Co=10??F, Lo=3.9mH Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic] Applicable Standard: EN IEC 60079-0, EN 60079-11 Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU II 3 G Ex ic IIC T5...T4 Gc Ambient Temperature: ?C30 to +70??C for T4, ?C30 to +50??C for T5 Enclosure: IP66/IP67 Overvoltage category: I Electrical parameters: Supply/Output circuit: Terminals: +, ?C Ui=30V, Ci=22nF, Li=0mH Sensor circuit: Terminals: 1, 2, 3, 4, 5 Uo=6V, Io=90mA, Po=135mW, Co=10??F, Lo=3.9mH Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval] Applicable Standard: EN IEC 60079-0, EN 60079-1, EN 60079-31 Certificate: KEMA 07ATEX0130X II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex tb IIIC T70??C/T90??C Db Ambient Temperature for Gas Atmospheres: ?C40 to 75??C for T6, ?C40 to 80??C for T5 Ambient Temperature for Dust Atmospheres: ?C30 to 65??C for T70??C, ?C30 to 80??C for T90??C Enclosure: IP66/IP67 Electrical Connection: 1/2 NPT female and M20 female(1) |