shoping-cartYour cart is empty
    Sign In or Register



    Sign In Socially

    If you are a member of facebook or google or yahoo, you can login to our system by clicking on the icon below.


YTA610-JA1A2DN/A/KU2+DOC-TC New Yokogawa YTA610 Temperature Transmitter

YTA610-JA1A2DN/A/KU2+DOC-TC New Yokogawa YTA610 Temperature Transmitter

$1,356.00  $664.00
Save: 51% off


Part Number: YTA610-JA1A2DN/A/KU2+DOC-TC
Model: YTA610 Temperature Transmitter
Manufacturer: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months

Ordering Information

Model YTA610 YTA610 Temperature Transmitter
Output signal -J 4 to 20 mA DC with digital communication HART 7 protocol
A Always A
Sensor input 1 Single
Housing code A Aluminum
Electrical connection 2 1/2 NPT female
Integral indicator D Digital indicator with Local Operating Switch
Mounting bracket N None
Lighting protector /A Allowable current: Max. 6000A(8x20??s), repeating 1000A(8x20??s), 100 times
ATEX /KU2 4-20mA:
[Intrinsically safe ia approval]
     Applicable Standard: EN IEC 60079-0, EN 60079-11
     Certificate No. FM16ATEX0019X
     II 1 G Ex ia IIC T5??T4 Ga
     II 2 (1) D Ex ia [ia Da] IIIC T135??C Db
     Ambient Temperature: ?C40 to +70??C for T4, ?C40 to +50??C for T5, ?C30 to +70??C for IIIC
     Enclosure: IP66/IP67
     Electrical parameters:
          Supply/Output circuit: Terminals: +, ?C
          Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
          Sensor circuit: Terminals: 1, 2, 3, 4, 5
          Uo=6V, Io=90mA, Po=135mW, Co=10??F, Lo=3.9mH
     Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic]
     Applicable Standard: EN IEC 60079-0, EN 60079-11
     Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU
     II 3 G Ex ic IIC T5...T4 Gc
     Ambient Temperature: ?C30 to +70??C for T4, ?C30 to +50??C for T5
     Enclosure: IP66/IP67
     Overvoltage category: I
     Electrical parameters:
          Supply/Output circuit: Terminals: +, ?C
          Ui=30V, Ci=22nF, Li=0mH
          Sensor circuit: Terminals: 1, 2, 3, 4, 5
          Uo=6V, Io=90mA, Po=135mW, Co=10??F, Lo=3.9mH
     Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
     Applicable Standard: EN IEC 60079-0, EN 60079-1, EN 60079-31
     Certificate: KEMA 07ATEX0130X
     II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex tb IIIC T70??C/T90??C Db
     Ambient Temperature for Gas Atmospheres: ?C40 to 75??C for T6, ?C40 to 80??C for T5
     Ambient Temperature for Dust Atmospheres: ?C30 to 65??C for T70??C, ?C30 to 80??C for T90??C
     Enclosure: IP66/IP67
     Electrical Connection: 1/2 NPT female and M20 female(3)

+DOC

-TC

  1. Applicable for Electrical Connection Code 2 and 4.


  • Estimated Lead Time: 8 - 10
  • Shipping Weight: 4 Kg

Add to Cart:

  • Model: YTA610-JA1A2DN/A/KU2+DOC-TC
  • 7 Units in Stock


Processing Time
  • Ships in 24 hours: Processing Time is guaranteed to be shorter than 24 hours.
  • Typical Processing Time: 3 - 12 days

We ship to over 200 countries worldwide!