Model | 1794-OB8EP |
Number of outputs
| 8, current, sourcing |
Recommended terminal base unit
| 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK |
On-state voltage, min | 19.2V DC |
On-state voltage, output nom | 24V DC |
On-state voltage, output max | 31.2V DC |
Output current rating | 2.0 A max per output 10.0 A max per module (8 outputs @ 1.25 A, 5 outputs @ 2.0 A, or similar combinations totaling 10.0 A or less) |
On-state current, output, min | 1.0 mA per channel |
On-state current, output, max | 2.0 A per channel |
On-state voltage drop, max | 0.2V DC |
Surge current | 4 A for 50 ms, repeatable every 3 seconds |
Off-state leakage current, max | 0.5 mA |
Isolation voltage
| 50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s, between field side and system No isolation between individual channels |
Output signal delay1 Off to On On to Off | 0.1 ms 0.1 ms |
FlexBus current | 73 mA @ 5V DC |
Power dissipation, max | 5.5 W @ 31.2V DC |
Thermal dissipation, max | 18.8 BTU/hr @ 31.2V DC |
Fusing | Outputs are electronically fused |